PIPING INSPECTION CODE: IN-SERVICE INSPECTION, RATING, REPAIR, AND
ALTERATION OF PIPING SYSTEMS
CORROSION RATES AND INSPECTION INTERVALS
Oleh : Bayu Nurwinanto
CMLS (Condition
monitoring location)
General
CMLs are specific areas along the piping circuit where
inspections are to be made. The nature of the CML varies according to its
location in the piping system. The selection of CMLs shall consider the
potential for localized corrosion and service-specific corrosion as described
in API 574 and API 571.
Examples of different types of CMLS include locations for thickness
measurement, locations for stress cracking examinations, locations for CUI and
locations for high temperature hydrogen attack examinations.
CML Monitoring
Each piping system shall be monitored at CMLs. Piping
circuits with high potential consequences of failure should occur and those
subject to higher corrosion rates or localized corrosion will normally have
more CMLs and be monitored more frequently. CMLs should be distributed
appropriately throughout each piping circuit. CMLs may be eliminated or the
number reduced under certain circumstances, such as olefin plant cold side
piping, anhydrous ammonia piping, clean noncorrosive hydrocarbon product, or
high-alloy piping for product purity. In circumstances where CMLS will be
substantially reduced or eliminated, persons knowledgeable in corrosion should
be consulted.
The minimum thickness at each CML can be located by
ultrasonic scanning or radiography. Electromagnetic techniques also can be used
to identify thin areas that may then be measured by UT or radiography. When
accomplished with UT, scanning consists of taking several thickness
measurements at the CML searching for localized thinning. The thinnest reading
or an average of several measurement readings taken within the area of a
examination point shall be recorded and used to calculate corrosion rates,
remaining life.
Where appropriate, thickness measurements should
include measurements at each of the four quadrants on pipe and fittings, with
special attention to the inside and outside radius of elbows and tees where
corrosion/erosion could increase corrosion rates. As a minimum, the thinnest
reading and its location shall be recorded. The rate of corrosion/ damage shall
be determined from successive measurements and the next inspection interval
appropriately established. Corrosion rates, the remaining life and next
inspection intervals should be calculated to determine the limiting component
of each piping circuit.
CMLS should be established for areas with continuing
CUI (Corrosion under insulation, including stress corrosion cracking under
insulation), corrosion at S/A interfaces, or other locations of potential
localized corrosion as well as for general, uniform corrosion.
CMLS should be marked on inspection drawings and on
the piping system to allow repetitive measurements at the same CMLS. This
recording procedure provides data for more accurate corrosion rate
determination. The rate of corrosion/damage shall be determined from successive
measurements and the next inspection interval appropriately established based
on the remaining life or RBI (risk-based inspection) analysis.
CML Selection
In selecting or adjusting the number and locations of
CMLS, the inspector should take into account the patterns of corrosion that
would be expected and have been experienced in the process unit. A decision on
the type, number and location of the CMLS should consider results from previous
inspections, the patterns of corrosion and damage that are expected and the
potential consequence of loss of containment. CMLS should be distributed
appropriately over the piping system to provide adequate monitoring coverage of
major components and nozzles. Thickness measurements at CMLS are intended to
establish general and localized corrosion rates in different sections of the
piping circuits. A minimal number of CMLS are acceptable when the established
corrosion rate is low and the corrosion is not localized.
A number of corrosion processes common to refining and
petrochemical units are relatively uniform in nature, resulting in a fairly
constant rate of pipe wall reduction independent of location within the piping
circuit, either axially or circumferentially. Examples of such corrosion
phenomena include high-temperature sulfur corrosion and sour water corrosion
(provided velocities are not so high as to cause local corrosion/erosion of
elbows, tees, and other similar items). In these situations, the number of CMLS required to monitor a circuit will be fewer than those required to monitor
circuits subject to more localized metal loss. In theory, a circuit subject to
perfectly uniform corrosion could be adequately monitored with a single CML. In
reality, corrosion is never truly uniform and in fact may be quite localized,
so additional CMLS may be required. Inspectors must use their knowledge (and
that of others) of the process unit to optimize the CML selection for each circuit,
balancing the effort of collecting the data with the benefits provided by the
data.
More CMLs (Condition monitoring location) should be selected for piping systems with any of the
following characteristics :
- higher potential for creating a safety or environmental emergency in the event of a leak.
- higher expected or experienced corrosion rates.
- higher potential for localized corrosion.
- more complexity in terms of fittings, branches, deadlegs, injection points, and other similar items.
- higher potential for CUI (corrosion under insulation, including stress corrosion cracking under insulation).
- low potential for creating a safety or environmental emergency in the event of a leak.
- relatively noncorrosive piping systems.
- long, straight-run piping systems.
- extremely low potential for creating a safety or environmental emergency in the event of a leak.
- noncorrosive systems, as demonstrated by history or similar service; and
- systems not subject to changes that could cause corrosion as demonstrated by history and/or periodic reviews.
- locations marked on un-insulated pipe using paint stencils, metal stencils, or stickers.
- holes cut in the insulation and plugged with covers.
- temporary insulation covers for fittings nozzles, etc.
- isometrics or documents showing CMLS.
- radio frequency identification devices (RFID).
Corrosion specialists should be consulted about the
appropriate placement and number of CMLs for piping systemssusceptible to
localized corrosion or cracking, or in circumstances where CMLs will be
substantially reduced or eliminated.
Inspection Intervals
If RBI ( risk-based inspection) is not being used, the interval between piping
inspections shall be established and maintained using the following criteria :
- corrosion rate and remaining life calculations.
- piping service classification.
- applicable jurisdictional requirements.
- judgment of the inspector, the piping engineer, the piping engineer supervisor, or a materials specialist, based on operating conditions, previous inspection history, current inspection results, and conditions that may warrant supplemental inspections.
Thickness measurements should be scheduled at
intervals that do not exceed the lesser of one half the remaining life
determined from corrosion rates or the maximum intervals recommended in Table. Shorter intervals may be appropriate under certain circumstances. Prior to
using Table, corrosion rates shall be calculated.
Table contains recommended maximum inspection
intervals for Classes 1, 2 and 3 of piping services, as well as recommended
intervals for injection points and S/A interfaces. Maximum intervals for Class
4 piping are left to the determination of the owner/user depending upon
reliability and business needs.
The inspection interval shall be reviewed and adjusted
as necessary after each inspection or significant change in operating
conditions. General corrosion, localized corrosion, pitting, environmental
cracking, and other applicable forms of deterioration mentioned in Section 5
shall be considered when establishing the various inspection intervals.
CUI (corrosion
under insulation, including stress corrosion cracking under insulation) Inspection.
Inspection for CUI shall be considered for
externally-insulated piping in areas or temperature ranges that are susceptible
to CUI. CUI inspections may be conducted as part of the external
inspection. If CUI damage is found during spot checks, the inspector should
inspect other susceptible areas on the equipment.
Although external insulation may appear to be in good
condition, CUI damage may still be occurring. CUI inspection may require
removal of some or all insulation. If external coverings are in good condition
and there is no reason to suspect damage behind them, it is not necessary to
remove them for inspection of the equipment. CUI damage is often quite
insidious in that it can occur in areas where it seems unlikely.
Considerations for insulation removal are not limited
to but include :
- history of CUI for the specific piping system or comparable piping systems.
- visual condition of the external covering and insulation.
- evidence of fluid leakage (e.g. stains or vapors).
- whether the piping systems are in intermittent service.
- condition/age of the external coating, if known.
- evidence of areas with wet insulation.
- the type of insulation used and whether that insulation is known to absorb and hold water.
General
All process piping systems shall be categorized into
different piping classes. Such a classification system allows extra inspection
efforts to be focused on piping systems that may have the highest potential
consequences if failure or loss of containment should occur. In general, the higher
classified systems require more extensive inspection at shorter intervals in
order to affirm their integrity for continued safe operation. Classifications
should be based on potential safety and environmental effects should a leak
occur.
Owner/users shall maintain a record of process piping
fluids handled, including their classifications. API 750 and NFPA 704 provide information that may be
helpful in classifying piping systems according to the potential hazards of the
process fluids they contain.
Class 1
Services with the highest potential of resulting in an
immediate emergency if a leak were to occur are in Class 1. Such an emergency
may be safety or environmental in nature. Examples of Class 1 piping include,
but are not necessarily limited to those containing the following.
- Flammable services that can autorefrigerate and lead to brittle fracture.
- Pressurized services that can rapidly vaporize during release, creating vapors that can collect and form an explosive mixture, such as C2, C3, and C4 streams. Fluids that can rapidly vaporize are those with atmospheric boiling temperatures below 50 °F (10 °C) or where the atmospheric boiling point is below the operating temperature (typically a concern with high-temperature services)
- Hydrogen sulfide (greater than 3 % weight) in a gaseous stream.
- Anhydrous hydrogen chloride.
- Hydrofluoric acid.
- Piping over or adjacent to water and piping over public throughways (refer to Department of Transportation and U.S. Coast Guard regulations for inspection of over water piping).
- Flammable services operating above their auto-ignition temperature.
Services not included in other classes are in Class 2.
This classification includes the majority of unit process piping and selected off-site
piping. Typical examples of these services include but are not necessarily
limited to those containing the following :
- on-site hydrocarbons that will slowly vaporize during release such as those operating below the flash point.
- hydrogen, fuel gas, and natural gas.
- on-site strong acids and caustics.
Services that are flammable but do not significantly
vaporize when they leak and are not located in high-activity areas are in Class
3. Services that are potentially harmful to human tissue but are located in
remote areas may be included in this class. Examples of Class 3 service include
but are not necessarily limited to those containing the following :
- on-site hydrocarbons that will not significantly vaporize during release such as those operating below the flash point.
- distillate and product lines to and from storage and loading.
- tank farm piping.
- off-site acids and caustics.
Services that are essentially nonflammable and
nontoxic are in Class 4, as are most utility services. Inspection of Class 4
piping is optional and usually based on reliability needs and business impacts
as opposed to safety or environmental impact. Examples of Class 4 service
include, but are not necessarily limited to those containing the following :
- steam and steam condensate.
- air.
- nitrogen.
- water, including boiler feed water, stripped sour water.
- lube oil, seal oil.
- ASME B31.3, Category D services.
- plumbing and sewers.
Assessment of Inspection Findings
Pressure containing components found to have
degradation that could affect their load carrying capability [pressure loads
and other applicable loads (e.g. weight, wind, etc., per API 579-1/ASME FFS-1)]
shall be evaluated for continued service. Fitness-For-Service techniques, such
as those documented in API
579-1/ASME FFS-1, Second Edition, may be used for this evaluation. The
Fitness-For-Service techniques used shall be applicable to the specific
degradation observed. The following techniques may be used as applicable.
To evaluate metal loss in excess of the corrosion
allowance, a Fitness-For-Service assessment may be performed in accordance with
one of the following sections of API 579-1/ASME FFS-1. This assessment requires the use of a
future corrosion allowance, which shall be established.
- Assessment of General Metal Loss—API 579-1/ASME FFS-1.
- Assessment of Local Metal Loss—API 579-1/ASME FFS-1.
- Assessment of Pitting Corrosion—API 579-1/ASME FFS-1.
To evaluate weld misalignment and shell distortions, a
Fitness-For-Service assessment should be performed in accordance with API 579-1/ASME FFS-1.
To evaluate crack-like flaws, a Fitness-For-Service
assessment should be performed in accordance with API 5791/ASME FFS-1.
To evaluate the effects of
fire damage, a Fitness-For-Service assessment should be performed in accordance
with API 579-1/ASME FFS-1.
Piping Stress Analysis (Analisis Piping Stres)
Piping shall be supported and guided so that :
- its weight is carried safely.
- it has sufficient flexibility for thermal expansion or contraction, and.
- it does not vibrate excessively.
Piping stress analysis to assess system flexibility
and support adequacy is not normally performed as part of a piping inspection.
However, many existing piping systems were analyzed as part of their original
design or as part of a rerating or modification, and the results of these
analyses can be useful in developing inspection plans. When unexpected movement
of a piping system is observed, such as during an external visual inspection the
inspector should discuss these observations with the piping engineer and
evaluate the need for conducting a piping stress analysis.
See API 574
for more information on pressure design, minimum required and structural
minimum thicknesses, including formulas, example problems and default tables of
suggested.
Piping stress analysis can identify the most highly
stressed components in a piping system and predict the thermal movement of the
system when it is placed in operation. This information can be used to
concentrate inspection efforts at the locations most prone to fatigue damage
from thermal expansion (heat-up and cooldown) cycles and/or creep damage in
high-temperature piping. Comparing predicted thermal movements with observed
movements can help identify the occurrence of unexpected operating conditions and
deterioration of guides and supports. Consultation with the piping engineer may
be necessary to explain observed deviations from the analysis predictions,
particularly for complicated systems involving multiple supports and guides
between end points.
Piping stress analysis also can be employed to help
solve observed piping vibration problems. The natural frequencies in which a
piping system will vibrate can be predicted by analysis. The effects of
additional guiding can be evaluated to assess its ability to control vibration
by increasing the system’s natural frequencies beyond the frequency of exciting
forces, such as machine rotational speed. It is important to determine that
guides added to control vibration do not adversely restrict thermal expansion.
Plant operators face known and unknown risks concerning asset integrity, especially at the touchpoints. Ovolifts unique and patented
ReplyDeletetechnology allows access to multiple touchpoints whilst the line is in-service. Corrosion
Under Pipe Support